| Standards and applications |
This series of cables are produced according to GB12527-90、GB14049-93and can be applied for aerial transmission and distribution lines with a rated AC voltage of 35kV and lower. |
| Properties |
| 1.The rated voltages are 0.6/1kV10kV35kV 2.The working temperature of the PVC/PE insulated cable during long-term service shall be lower than 70℃, and XLPE insulated cable shallbe lower than 90℃. 3.The environmental temperature when laying shall be higher than -20℃ 4.Tthe allowable bending radius: cable outer diameter (D) smaller than 25mm: the allowable bending radius shall be larger than 4D; cable outer diameter(D) equal to or larger than 25mm: the allowable bending radius shall be larger than 6D 5.Under AC power, the cable’s rated voltage shall be no less than that of the AC power; Under DC power, the rated voltage shall be smaller than1.5 times of the cable’s rated voltage. |